UL 1685 Smoke Release Test for Electrical and Fiber Optic Cables

Electric Electronic Tests

UL 1685 Smoke Release Test for Electrical and Fiber Optic Cables

EUROLAB laboratory provides testing and compliance services within the scope of UL 1685 standard. This standard is a vertical tray fire test to determine values ​​for flame exposure, cable damage.

UL 1685 Smoke Release Test for Electrical and Fiber Optic Cables

For a cable to be acceptable under the UL testing procedure, each of the following must be demonstrated:

  • Cable character height will be less than 8 ft. 0 inches (244 cm) when measured from a distance. the lower part of the conduit according to Section 8.
  • The total smoke emitted will be 95 m 2 or less.
  • Peak smoke emission rate will be 0,25 m2/s or less.

The purpose of this test is to determine the flame spread and smoke characteristics of these cables in order to qualify them for limited smoke marking.

This test does not investigate the toxicity of combustion or decomposition products.

This test does not cover the structural requirements of the cable or any electrical, optical or other performance requirements for the cable.

EUROLAB assists manufacturers with UL 1685 test compliance. Our test experts, with their professional working mission and principles, provide you, our manufacturers and suppliers, the best service and controlled testing process in our laboratories. Thanks to these services, businesses receive more effective, high-performance and quality testing services and provide safe, fast and uninterrupted service to their customers.